# Growatt 60: Negative power fault

**Series:** Growatt SPF 3500/5000 ES off-grid solar inverter

**Meaning:** A negative power condition, typically a parallel-system wiring or configuration problem.

## Likely causes
- AC output connected to the grid input
- Mismatched program 8 settings across parallel inverters
- Poor current-sharing cable or neutral connections

## Checks
- Check the AC output is not connected to the grid input
- Check program 8 settings match on all parallel inverters
- Check current-sharing cables and that all neutral wires of parallel units are connected together

## Parts implicated
AC wiring, parallel cabling

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: grid_tie

## Provenance
- [manual] p. 40 — "Negative power fault. — Check whether the AC output connected to the grid input. Check whether Program 8 settings are the same for all parallel inverters. Check whether the current sharing cables are connected well in the same parallel phases. Check whether all neutral wires of all parallel units are connected together." — https://en.growatt.com/upload/file/SPF_3500-5000_ES_User_Manual_EN_202109.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: yes