# SMA 105: Grid incident - grid voltage or grid impedance too high

**Series:** SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)

**Meaning:** Events 101, 102, 103, 104 and 105 all report the same thing: the grid voltage or grid impedance at the inverter's connection point is too high, so the Sunny Tripower has disconnected from the utility grid. SMA's corrective measures are to verify that the grid voltage stays permanently inside the permissible range and, where the local grid is responsible, to have the grid operator adjust the voltage at the feed-in point or change the monitored operating limits.

## Likely causes
- Grid voltage above the permissible range at the connection point
- High grid impedance on a weak or long grid connection
- Monitored operating limits not matching the local grid conditions

## Checks
- Check whether the grid voltage at the connection point is permanently within the permissible range
- If local grid conditions keep it out of range, ask the grid operator to adjust the feed-in voltage or the monitored operating limits
- If the voltage is in range and the message persists, contact SMA Service

## Parts implicated
grid connection

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: grid_tie

## Provenance
- [manual] p. 81 — "Explanation: The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid." — https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: yes