# SMA 1101: Installation fault - check connection

**Series:** SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)

**Meaning:** A second line conductor has been connected to the neutral terminal N. The manual's corrective measure is to connect the neutral conductor to N, which means correcting the AC terminal wiring at the inverter.

## Likely causes
- Two line conductors landed on N
- AC terminal wiring error at installation

## Checks
- Isolate the AC supply and prove dead
- Connect the neutral conductor to N
- Re-check the terminal assignment before re-energising

## Parts implicated
AC wiring, AC terminal

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: grid_tie

## Provenance
- [manual] p. 88 — "Explanation: A second line conductor is connected to N." — https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: yes