# SMA 6512: Minimum operating temperature not reached

**Series:** SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)

**Meaning:** The inverter is colder than its minimum operating temperature and will only recommence grid feed-in once the temperature has reached at least -25 °C. There is no repair: the installation site is simply too cold for the unit to run.

## Likely causes
- Ambient or enclosure temperature below -25 °C
- Inverter mounted in an exposed location without shelter

## Checks
- Measure the ambient temperature at the inverter
- Compare the site temperature range with the datasheet operating range
- Shelter or relocate the inverter if the site falls outside that range

## Parts implicated
none

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: none

## Provenance
- [manual] p. 94 — "Explanation: The inverter will only recommence grid feed-in once the temperature has reached at least −25°C." — https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: no