# SolarEdge 2x11: Temperature too high

**Series:** SolarEdge single-phase and three-phase inverters (Europe & APAC)

**Meaning:** The inverter's internal temperature exceeded its limit. The addendum says to verify proper inverter clearances and make sure the heat-sink fins are clean and unobstructed.

## Likely causes
- Blocked airflow around the inverter
- Dirty or obstructed heat-sink fins
- High ambient temperature at the mounting location

## Checks
- Verify the clearances around the inverter match the installation guide
- Check that the heat-sink fins are clean and unobstructed
- Measure the ambient temperature at the mounting location

## Parts implicated
heat sink, cooling

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: none

## Provenance
- [manual] p. 3 — "Temperature Too High Over temperature Verify proper inverter clearances. Make sure the heat-sink fins are clean and unobstructed." — https://web.archive.org/web/20230202122919/https://knowledge-center.solaredge.com/sites/kc/files/se-inverter-installation-guide-error-codes.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: yes