# SolarEdge 2x1F: AC voltage too high (line 1/2/3)

**Series:** SolarEdge single-phase and three-phase inverters (Europe & APAC)

**Meaning:** The grid voltage on one AC line rose above the country limit, so the inverter tripped. The addendum says to verify the country setting, turn the site's inverters off and verify the AC grid voltage, use a larger gauge AC wire on long runs, consult the grid operator and, where permitted, change the grid protection values.

## Likely causes
- Grid over-voltage above the country limit
- Inverter set to the wrong country
- Voltage rise on an undersized AC cable

## Checks
- Verify the inverter is set to the correct country
- Turn off the site's inverters and measure the AC grid voltage
- Use a larger gauge AC wire if the inverter is far from the grid connection point
- Consult the grid operator and change grid protection values only where local rules permit

## Parts implicated
AC wiring

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: grid_tie

## Provenance
- [manual] p. 3 — "AC Voltage Too High (Line 1/2/3) Grid voltage is above the country limit." — https://web.archive.org/web/20230202122919/https://knowledge-center.solaredge.com/sites/kc/files/se-inverter-installation-guide-error-codes.pdf (retrieved 2026-11-21)

- Confidence: verified
- Verified by: manual
- Requires qualified installer: yes