# Victron Err 42: PV isolation failure (ground leakage)

**Series:** Victron SmartSolar / BlueSolar MPPT charge controllers, Inverter RS / Multi RS, Orion Smart DC-DC

**Meaning:** Ground leakage current in the PV array exceeds the 30 mA limit.

## Likely causes
- Damaged PV cabling or panel insulation
- Moisture or ground leakage in the array

## Checks
- Check PV array cabling and panel isolation
- Disconnect the PV array with the PV switch to resume AC operation

## Parts implicated
PV cabling, panels

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: dc_arc, pv_dc

## Provenance
- [vendor_kb] § Err 42 - PV isolation failure — "The ground leakage current in the PV array exceeds the allowed 30mA limit. Check the PV array cabling and panel isolation. Consider disconnecting the PV array using the PV switch to resume AC operation." — https://www.victronenergy.com/live/mppt-error-codes (retrieved 2026-11-21)