# Victron Err 57: Inverter AC voltage on output

**Series:** Victron SmartSolar / BlueSolar MPPT charge controllers, Inverter RS / Multi RS, Orion Smart DC-DC

**Meaning:** There is already AC voltage on the AC-out terminal before the inverter switches on, e.g. AC-out is connected to a mains outlet or another inverter. It does not auto-reset.

## Likely causes
- AC-out connected to mains or another inverter

## Checks
- Check the AC-out is not connected to a mains outlet or another inverter
- Correct the installation and restart with the power switch

## Parts implicated
AC-out wiring

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: grid_tie

## Provenance
- [vendor_kb] § Err 57 - Inverter ac voltage on output — "There is already AC voltage on the AC out terminal before switching on the inverter." — https://www.victronenergy.com/live/mppt-error-codes (retrieved 2026-11-21)

- Confidence: verified
- Verified by: vendor_kb
- Requires qualified installer: yes