# Victron VE.Bus Error 1: Device switched off because another phase switched off

**Series:** Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

**Meaning:** In a multi-phase system one phase has failed (commonly low battery, overload, or high temperature), so the other phases report Error 1 and switch off.

## Likely causes
- Low battery, overload, or high temperature on one phase

## Checks
- Find the failing phase (the one NOT showing Error 1) and read its LEDs for overload / low battery / temperature
- Check the alarm log on the GX device or VRM while the fault is present

## Parts implicated
battery, AC loads

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: dc_bus, grid_tie, lithium_battery

## Provenance
- [vendor_kb] § Error 1 - Device is switched off because one of the other phases in the system has switched off — "One of the phases in a multi-phase system has failed." — https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes (retrieved 2026-11-21)

- Confidence: verified
- Verified by: vendor_kb
- Requires qualified installer: yes