# Victron VE.Bus Error 11: Relay test fault (installation or relay failure)

**Series:** Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

**Meaning:** A failed automatic self-test of the MultiPlus-II / EasySolar-II relays; usually an installation or wiring issue, but can be a hardware failure.

## Likely causes
- Earth not grounded per local grid rules, or Earth connected to Neutral in the unit
- AC-in Line/Neutral inverted
- Leakage between load, neutral and ground
- Faulty relay

## Checks
- Update firmware to latest
- Verify the earth connection and that Earth is not connected to Neutral in the unit
- Isolate AC-out (disconnect L and N) and test
- Check the Neutral-out / Neutral-in connection per grid code
- Check Line/Neutral are not swapped

## Parts implicated
relay, AC wiring, earthing

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: dc_bus, grid_tie, pv_dc

## Provenance
- [vendor_kb] § Error 11 - Relay Test Fault - Installation error or possibly relay failure — "Error 11 indicates a failed automatic self-test of the MultiPlus-II or EasySolar-II relays." — https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes (retrieved 2026-11-21)

- Confidence: verified
- Verified by: vendor_kb
- Requires qualified installer: yes