# Victron VE.Bus Error 6: Error in DDC program (Assistant)

**Series:** Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

**Meaning:** An error in a configured Assistant. Fix by updating firmware and VEConfigure Assistants and re-configuring the system; can also follow connecting a VE.Bus BMS without the matching Assistant.

## Likely causes
- Outdated firmware or Assistants
- VE.Bus BMS connected without a matching Assistant

## Checks
- Update VE.Bus firmware on all devices
- Update VEConfigure and its Assistants, then re-configure
- Configure a matching Assistant if a VE.Bus BMS is connected

## Parts implicated
firmware, configuration

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: dc_bus, lithium_battery

## Provenance
- [vendor_kb] § Error 6 - Error in DDC Program — "This means: error in an Assistant." — https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes (retrieved 2026-11-21)

- Confidence: verified
- Verified by: vendor_kb
- Requires qualified installer: yes