# Victron VE.Bus Error 8: Ground relay test failed

**Series:** Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

**Meaning:** A failed self-test of the internal ground relay (MultiPlus-II / EasySolar-II). The ground relay is tested to close during inverting and to open when switching to mains.

## Likely causes
- Neutral-out externally tied to ground
- Intentional Neutral bypass not configured in software
- Leakage or short in the AC loads
- Faulty ground relay or detection circuit

## Checks
- Check Neutral-out is not externally tied to ground
- Check the neutral path configuration matches the grid code
- Isolate loads (open breakers) and retest grid switch-over
- Replace the unit if a ground-relay error repeats

## Parts implicated
ground relay, AC wiring

## Safety
Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. This page is a diagnostic reference, not step-by-step work instructions. Isolate and verify de-energised before any physical check, and escalate to a qualified installer/electrician for anything beyond reading the display or checking a connector on isolated equipment.

Safety flags: dc_bus, grid_tie, pv_dc

## Provenance
- [vendor_kb] § Error 8 - Ground relay test failed — "This error indicates a failed self-test of the MultiPlus-II or EasySolar-II internal 1 ground relays." — https://www.victronenergy.com/live/ve.bus:ve.bus_error_codes (retrieved 2026-11-21)

- Confidence: verified
- Verified by: vendor_kb
- Requires qualified installer: yes