Growatt SPF 3500/5000 ES off-grid solar inverter
Growatt 60: Negative power fault
Quick answerGrowatt 60 means A negative power condition, typically a parallel-system wiring or configuration problem..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.
What it means
A negative power condition, typically a parallel-system wiring or configuration problem.
Likely causes
- AC output connected to the grid input
- Mismatched program 8 settings across parallel inverters
- Poor current-sharing cable or neutral connections
What to check
- Check the AC output is not connected to the grid input
- Check program 8 settings match on all parallel inverters
- Check current-sharing cables and that all neutral wires of parallel units are connected together
Parts implicated
AC wiringparallel cabling
Sources (verbatim):
- https://en.growatt.com/upload/file/SPF_3500-5000_ES_User_Manual_EN_202109.pdf (manual, retrieved 2026-11-21) p. 40
“Negative power fault. — Check whether the AC output connected to the grid input. Check whether Program 8 settings are the same for all parallel inverters. Check whether the current sharing cables are connected well in the same parallel phases. Check whether all neutral wires of all parallel units are connected together.”
Paraphrased; verify against the manual for your exact model and serial number.