SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)

SMA 1501: Reconnection fault grid

confidence: verifiedchecked 2026-11-21
Quick answerSMA 1501 means The changed country standard, or the value of a parameter that was set, does not correspond to the local requirements, so the inverter cannot connect to the utility grid. SMA's remedy is to select the parameter 'Set country standard' and check its value..
Escalation. If the fix goes beyond a non-invasive check or a software setting, or you are not sure the system is isolated, stop and call a qualified installer.

What it means

The changed country standard, or the value of a parameter that was set, does not correspond to the local requirements, so the inverter cannot connect to the utility grid. SMA's remedy is to select the parameter 'Set country standard' and check its value.

Likely causes

  • Country standard not matching the site's grid code
  • A grid parameter set outside the local requirements

What to check

  1. Select the parameter Set country standard and check its value
  2. Correct the country standard to match the local grid requirements
  3. Re-commission and confirm the inverter connects to the grid

Parts implicated

grid connection