SMA Sunny Tripower 3.0 / 4.0 / 5.0 / 6.0 (STPxx-3AV-40)
SMA 901: PE connection missing - check connection
Quick answerSMA 901 means The inverter reports that the grounding conductor is not correctly connected, so the protective earth path it relies on is absent. The manual's single corrective measure is to ensure that the grounding conductor is correctly connected before the inverter is put back into service..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.
What it means
The inverter reports that the grounding conductor is not correctly connected, so the protective earth path it relies on is absent. The manual's single corrective measure is to ensure that the grounding conductor is correctly connected before the inverter is put back into service.
Likely causes
- Protective earth conductor not landed on the inverter
- Loose, broken or missing PE conductor in the AC cable
What to check
- Isolate the inverter from voltage sources
- Ensure that the grounding conductor is correctly connected
- Verify PE continuity to the installation's earthing point before re-energising
Parts implicated
AC wiringprotective earth
Sources (verbatim):
- https://files.sma.de/downloads/STP3-6-3AV-40-BE-en-22.pdf (manual, retrieved 2026-11-21) p. 87
“Explanation: The grounding conductor is not correctly connected.”
Paraphrased; verify against the manual for your exact model and serial number.