SolarEdge single-phase and three-phase inverters (Europe & APAC)

SolarEdge 18x7F: IRCDMax (RCD current surge)

confidence: verifiedchecked 2026-11-21
Quick answerSolarEdge 18x7F means The inverter detected an RCD current surge caused by insufficient insulation to ground. The addendum repeats the isolation-fault procedure: switch off, wait five minutes, disconnect AC and DC, then reconnect strings one at a time to find the faulty string, which only a certified installer may fix..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

The inverter detected an RCD current surge caused by insufficient insulation to ground. The addendum repeats the isolation-fault procedure: switch off, wait five minutes, disconnect AC and DC, then reconnect strings one at a time to find the faulty string, which only a certified installer may fix.

Likely causes

  • Insufficient insulation to ground in the PV array
  • Damaged DC cable, connector or module
  • Water ingress causing leakage to earth

What to check

  1. Turn the inverter ON/OFF switch OFF and wait five minutes for the capacitors to discharge
  2. Disconnect the AC breaker and the DC inputs
  3. Reconnect each DC string separately until the error reappears
  4. Do not reconnect a grounded string; a certified installer must repair it

Parts implicated

PV modulesDC cablingRCD