SolarEdge single-phase and three-phase inverters (Europe & APAC)

SolarEdge 2x1F: AC voltage too high (line 1/2/3)

confidence: verifiedchecked 2026-11-21
Quick answerSolarEdge 2x1F means The grid voltage on one AC line rose above the country limit, so the inverter tripped. The addendum says to verify the country setting, turn the site's inverters off and verify the AC grid voltage, use a larger gauge AC wire on long runs, consult the grid operator and, where permitted, change the grid protection values..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

The grid voltage on one AC line rose above the country limit, so the inverter tripped. The addendum says to verify the country setting, turn the site's inverters off and verify the AC grid voltage, use a larger gauge AC wire on long runs, consult the grid operator and, where permitted, change the grid protection values.

Likely causes

  • Grid over-voltage above the country limit
  • Inverter set to the wrong country
  • Voltage rise on an undersized AC cable

What to check

  1. Verify the inverter is set to the correct country
  2. Turn off the site's inverters and measure the AC grid voltage
  3. Use a larger gauge AC wire if the inverter is far from the grid connection point
  4. Consult the grid operator and change grid protection values only where local rules permit

Parts implicated

AC wiring
Sources (verbatim):