SolarEdge single-phase and three-phase inverters (Europe & APAC)
SolarEdge 2x20: AC voltage too low
Quick answerSolarEdge 2x20 means The AC grid voltage the inverter measures is below the limit for the selected country. The addendum's remedy is to verify that the inverter is set to the correct country, then to consult the grid operator..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.
What it means
The AC grid voltage the inverter measures is below the limit for the selected country. The addendum's remedy is to verify that the inverter is set to the correct country, then to consult the grid operator.
Likely causes
- Grid under-voltage or a weak grid connection
- Inverter set to the wrong country/grid code
- Undersized or damaged AC cable causing voltage drop
What to check
- Verify that the inverter is set to the correct country
- Consult the grid operator about the supply voltage
- Check the AC cable size and terminations against the installation guide
Parts implicated
AC wiring
Sources (verbatim):
- https://web.archive.org/web/20230202122919/https://knowledge-center.solaredge.com/sites/kc/files/se-inverter-installation-guide-error-codes.pdf (manual, retrieved 2026-11-21) p. 3
“AC Voltage Too Low Verify that the inverter is set to the correct country.”
Paraphrased; verify against the manual for your exact model and serial number.