SolarEdge single-phase and three-phase inverters (Europe & APAC)

SolarEdge 2x22: AC frequency too high (line 1/2/3)

confidence: verifiedchecked 2026-11-21
Quick answerSolarEdge 2x22 means The inverter measured an AC grid frequency above the upper limit of the selected country grid code, so it disconnected from the grid. The addendum lists the message without a field repair; the cause is on the grid side or in the country setting..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

The inverter measured an AC grid frequency above the upper limit of the selected country grid code, so it disconnected from the grid. The addendum lists the message without a field repair; the cause is on the grid side or in the country setting.

Likely causes

  • Grid frequency excursion above the country limit
  • Inverter set to the wrong country/grid code
  • Local generator or backup source holding the frequency high

What to check

  1. Confirm the country/grid-code setting in SetApp
  2. Ask the grid operator whether a frequency excursion was recorded
  3. Check that no local generator is back-feeding the site

Parts implicated

AC wiring
Sources (verbatim):

Paraphrased; verify against the manual for your exact model and serial number.