Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. Read the safety model.
Victron SmartSolar / BlueSolar MPPT charge controllers, Inverter RS / Multi RS, Orion Smart DC-DC

Victron Err 39: PV input shutdown (over-voltage, auto-recover)

confidence: verifiedchecked 2026-11-21
Quick answerVictron Err 39 means The PV input was internally shorted to protect the battery from over-charging; the charger resumes automatically once battery voltage drops below its maximum voltage setting..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

The PV input was internally shorted to protect the battery from over-charging; the charger resumes automatically once battery voltage drops below its maximum voltage setting.

Likely causes

  • Battery voltage setting incorrect
  • Another device on the battery set to a higher voltage
  • Outdated firmware

What to check

  1. Update firmware
  2. Verify battery voltage settings
  3. Confirm the error clears as battery voltage falls

Parts implicated

batteryPV input
Sources (verbatim):
  • https://www.victronenergy.com/live/mppt-error-codes (vendor_kb, retrieved 2026-11-21) § Err 38, Err 39 and Err 80 to Err 87 - PV Input shutdown
    “When these errors show, the PV Input is internally shorted in order to protect the battery from over-charging.”

Paraphrased; verify against the manual for your exact model and serial number.