Victron SmartSolar / BlueSolar MPPT charge controllers, Inverter RS / Multi RS, Orion Smart DC-DC
Victron Err 43: Ground fault detected
Quick answerVictron Err 43 means The voltage between Neutral and Ground is too high. On grid-connected systems this usually means the installation ground is missing/incorrect or Line and Neutral are swapped; on island systems the ground relay may be damaged. It does not auto-reset..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.
What it means
The voltage between Neutral and Ground is too high. On grid-connected systems this usually means the installation ground is missing/incorrect or Line and Neutral are swapped; on island systems the ground relay may be damaged. It does not auto-reset.
Likely causes
- Missing or incorrectly connected ground wire
- Line and Neutral swapped in the installation
- Damaged ground relay (island operation)
What to check
- Check the installation ground and Line/Neutral wiring
- Restart the unit with the power switch after correcting the wiring
Parts implicated
ground wiringground relay
Sources (verbatim):
- https://www.victronenergy.com/live/mppt-error-codes (vendor_kb, retrieved 2026-11-21) § Err 43 - Ground fault detected
“The voltage difference between Neutral and Ground is too high.”
Paraphrased; verify against the manual for your exact model and serial number.