Qualified installer only. High-voltage, grid-tied and battery systems can kill. Do not open energised DC/AC equipment. Read the safety model.
Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

Victron VE.Bus Error 11: Relay test fault (installation or relay failure)

confidence: verifiedchecked 2026-11-21
Quick answerVictron VE.Bus Error 11 means A failed automatic self-test of the MultiPlus-II / EasySolar-II relays; usually an installation or wiring issue, but can be a hardware failure..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

A failed automatic self-test of the MultiPlus-II / EasySolar-II relays; usually an installation or wiring issue, but can be a hardware failure.

Likely causes

  • Earth not grounded per local grid rules, or Earth connected to Neutral in the unit
  • AC-in Line/Neutral inverted
  • Leakage between load, neutral and ground
  • Faulty relay

What to check

  1. Update firmware to latest
  2. Verify the earth connection and that Earth is not connected to Neutral in the unit
  3. Isolate AC-out (disconnect L and N) and test
  4. Check the Neutral-out / Neutral-in connection per grid code
  5. Check Line/Neutral are not swapped

Parts implicated

relayAC wiringearthing
Sources (verbatim):

Paraphrased; verify against the manual for your exact model and serial number.