Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

Victron VE.Bus Error 17: Phase master missing

confidence: verifiedchecked 2026-11-21
Quick answerVictron VE.Bus Error 17 means Shown on slaves when communication with the phase-master timed out. Only occurs with multiple devices per phase..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

Shown on slaves when communication with the phase-master timed out. Only occurs with multiple devices per phase.

Likely causes

  • VE.Bus cabling issue
  • Blown DC fuse on a unit
  • Outdated firmware/Assistants

What to check

  1. Check network cable sockets and replace cables if needed
  2. Check DC fuses on all units
  3. Update inverter/charger firmware, Assistants, and GX device firmware

Parts implicated

VE.Bus cablingDC fusefirmware