Victron MultiPlus / Quattro / MultiPlus-II / EasySolar-II (VE.Bus inverter/charger)

Victron VE.Bus Error 8: Ground relay test failed

confidence: verifiedchecked 2026-11-21
Quick answerVictron VE.Bus Error 8 means A failed self-test of the internal ground relay (MultiPlus-II / EasySolar-II). The ground relay is tested to close during inverting and to open when switching to mains..
Qualified installer only. This fault touches the AC grid connection, battery bank, DC bus, or an internal power stage. Isolate and verify de-energised, then escalate to a qualified installer/electrician.

What it means

A failed self-test of the internal ground relay (MultiPlus-II / EasySolar-II). The ground relay is tested to close during inverting and to open when switching to mains.

Likely causes

  • Neutral-out externally tied to ground
  • Intentional Neutral bypass not configured in software
  • Leakage or short in the AC loads
  • Faulty ground relay or detection circuit

What to check

  1. Check Neutral-out is not externally tied to ground
  2. Check the neutral path configuration matches the grid code
  3. Isolate loads (open breakers) and retest grid switch-over
  4. Replace the unit if a ground-relay error repeats

Parts implicated

ground relayAC wiring